CDP
32 Instruction Manual
• Disconnection condition:
< .
(
= 0%) 0% ≤ 50%
this condition is met
relay 2 stays connected
At this point, the CDP-G will check whether it can connect the third load. To do
so, it must verify whether the connection condition is met:
• Condition 1:
100 .
(
100 = 80%) 80% ≤ 90% this condition is met
• Condition 2:
-If Injection Margin = 0% It checks whether:
Pgrid < 2 x (0.03) x Pconsumed
-If Injection Margin ≠ 0% It checks whether:
Pgrid < 2 x Injection Margin x Pconsumed
0 < 2 x 0.03 x 8000 this condition is met
If the 2 conditions are met, the relay closes and connects load number 3.
(Figure 29)