There are several symptoms that may detect poor installation or setting of the
QNA-412:
The voltage measurements are flashing on the display. The causes may be:
The equipment has detected an event. This may mean that there has
actually been an event in the line (correct installation) or that the pre-set
nominal voltage does not match that of the system.
If the balance screen displays dashes: It means that the phase turn
sequence is wrong.
Power screens with a minus sign:
The installation is generating energy. Or actually, energy is being
generated or the current transformers are installed backwards.
The PF values are wrong. Check the voltage phases and current
connection. The voltage and current phase do not correspond to that
connected to the QNA.
8.- SETTING THE QNA-412.
The QNA-412 is always set via a PC.
The operation of the QNA-412 analyzer will depend on the setting of the
equipment. There are two types of Set-up:
Programming Set-up: This will define the QNA-412 analyzer's operating mode.
File setup: This will define the variables that the QNA-412 is to record in its
internal memory
8.1.- Programming Set-up for the QNA-412.
There is a complete series of parameters that may be set in the analyzer:
8.1.1.- Voltage transformation ratio.
The QNA-412 system analyzer has the option to measure voltage via
transformers.
Voltage primary / Voltage secondary: The voltage transformer ratio via
which the measurement shall be taken can be set. Where direct
measurements are to be made, this must be set as1/1.
Current primary: The current transformer primary used for measuring
current can be set.
Neutral current primary: The current transformer primary used for
measuring Neutral current can be set.