3.- TECHNICAL FEATURES
Power circuit:
- Single-phase (A1 A2) :
- Frequency:
- Maximum consumption:
- Working temperature:
- Humidity (no condensation) :
230 V
ac
± 15%
47…63 Hz
8 VA
-10 … +60 ºC
5 … 95%
- Flashing power LED
- Flashing RX/TX
- LINK/ACTIVITY
Powered unit and CPU activity
RS-485 frame delivery and reception activity
Flashing: Activity in the Ethernet bus
Green: Speed 10/100 Mb/s
Mechanical features:
- Case material:
- Unit protection degree:
- Dimensions (mm):
- Weight:
- Maximum operating height:
UL94 - V0 self-extinguishing plastic
IP 20
35.4 x 73 x 84.68 mm (2 modules)
120 g
2,000 m
Standards:
IEC 60664, VDE 0110, UL 94, EN61010-1, EN55011, EN 61000-4-2, EN 61000-4-3,
61000-4-11, EN 61000-6-4, EN 61000-6-2, EN 61000-6-1, EN 61000-6-3, EN 61000-4-5,
CE
Network interface:
- Type:
- Connector:
- Network Protocols - Accesses:
Ethernet 10BaseT / 100BaseTX self-detecting
RJ45
TCP / UDP / Modbus
Safety:
Installation category: Category III / EN61010 double-insulated electric shock protection
class II. The unit must be connected to a power circuit protected with type gl fuses, in
compliance with IEC 269, or type M, with values from 0.5 to 1A. It must be fitted with a
circuit breaker switch or equivalent device in order to be able to disconnect the unit from
the power supply. The power supply cable must have a minimum cross-section of 1 mm
2
.
If the unit is not operated according to the manufacturer's specifications, its guaranteed
degree of protection may be compromised.
Serial interface:
- Type:
- Transmission speed (configurable):
- Data bits:
- Parity:
- Stop bit
RS-485 three-wires (A/S/B) (RX/GND/TX)
1200, 2400, 4800, 9600,19200, 34800, 57600,
115200 baud rate
7, 8
No parity, odd, even
1 or 2
4.- CONNECTIONS
Figure 1. Standard connection of serial units
5.- TECHNICAL SERVICE
If you have any doubts about the operation of the unit or suspect any malfunction, contact our service staff at CIRCUTOR, SA
CIRCUTOR, SA - Technical Assistance Service
Vial Sant Jordi, s/n
08232 Viladecavalls (Barcelona), SPAIN
Tel.: 902 449 459 (Spain)
Tel.: (+34) 93 745 29 00 (Outside Spain)