M98236001-03-14A
6.- Modbus/RTU memory map
Partial Inductive Reactive Energy
Partial Capacitive Reactive Energy
Partial Reactive Energy (L/C)
FOUR QUADRANTS MEASUREMENT
Capacitive Inductive Power
Generated Inductive Reactive Energy
Generated Capacitive Reactive Energy
Generated Total Reactive Energy (L/C)
Partial Generated Active Energy
Inductive Reactive Energy
Partial Generated Inductive Reactive Energy
Capacitive Reactive Energy
Generated Capacitive Reactive Energy
Partial Generated Total Reactive Energy (L/C)
7.- CVM-1D communication
One or several -CVM-1D analyzers can be connected to a controller or PLC. Using this system you can operate each of the analyzers as usual as well as centralize the data in a single
location. CVM-1D incorporates an RS-485 type communications output. If more than one analyzer is connected to an RS-485 serial bus, each of them must be assigned a peripheral
number or address so that the communications master can send the queries regarding the different measured or calculated records to those addresses.the RS-485 connection is carried out
via the shielded twisted pair communication cable, with a minimum of two wires and with a maximum distance between the communications master and the last unit of 1,200 metros. The
device uses an RS-485 communications line that can support a maximum of 32 units in series per bus.
The CVM-1D type power analyzer communicates via a Modbus/RTU© protocol (Question / answer polling).
8.- Technical specifications
Supply specifications :
- Single-phase :
- Frequency:
- Maximum consumption :
88…276 V
c.a
50 / 60 Hz
2 VA
Metering circuit:
- Nominal voltage / Tolerance:
- Nominal voltage / MID Tolerance:
- Frequency :
- MID frequency:
- Nominal current/minimum/maximum:
- Start current (Ist):
- Reference current (Iref):
- Transition current (Itr):
110…230 V
c.a
/ ±20 %
230 V
c.a
/ ±20 %
50 / 60Hz
50Hz
5 A / 250 mA / 32 A
20 mA
5 A
500 mA
Mechanical specifications:
- Case material :
- Protection :
Fitted unit (front panel) :
Fitted MID unit (front panel) :
Non-fitted unit (front panel):
- Maximum Dimensions (mm) :
- Weight :
Selft-extinguish UL94-V0 plastic
IP31
IP51
IP20
85.5 x 64.2 x 18 mm (1 DIN rail module)
150 g
Output transistor specifications
- Typo: opto-isolated transistor (open
collector)
- Maximum operating voltage:
- Maximum operating current:
- Maximum frequency:
- Pulse width:
NPN
42 V
c.c.
50 mA
1000 imp / kW·h
40…200ms (configurable)
Environmental specifications:
- Working temperature:
- Storage temperature:
- Humidity:
- Maximum altitude:
-5...+45 ºC
-25...+70 ºC
5…95% non condensing
2000m
Safety:
CATIII-300 EN61010-1:2010 EN61010-2-030:2011. Double insulation. Pollution degree II.
Means for disconnecting the power from the device must be provided in the installation.
Wire conductor are must be choosen depending on current to flow acroos the device.
Minimum recommended wire is 1mm
2
Standards :
EN 50470-1, EN50470-3, EN62053-21, EN62053-23, EN61010-1:2010,
EN 61000-6-4, EN 55022
Energy meter: Class B EN50470-3 Active Energy, Class 2 EN62053-23 Reactive
Energy.
Accuracy:
- Voltage :
- Current :
- Power / Energy :
Sensors :
- Voltage :
- Current :
Power factor :
Measurement range:
0.5 % ± 1 digit
0.5 % ± 1 digit
1 % ± 1 digit
Direct. Impedance 1M
Direct (shunt <0,5 m)
0.5...1
0.5...120% FS
9.- Connections
Single-phase connection system
10.- Technical Service
If you have any doubts about the operation of the unit or suspect any malfunction, contact our service staff at CIRCUTOR, SA
CIRCUTOR, SA - Technical Assistance Service
Vial Sant Jordi, s/n
08232 – Viladecavalls (Barcelona),Spain
Tel: 902 449 459SPAIN
Tel: (+34) 93 745 29 00 (outside of Spain)
email: sat@circutor.es