PowerStudio PowerStudio
134 User Manual
Voltage transformation ratio: Primary and secondary voltage programming. The product of
the primary value and the primary current must be the same as or less than 20,000,000. The
value of the primary, depending on the fullscale of the equipment, must be between 1 and the
corresponding value from the following table:
Full-scale
Maximum value.
110V
99.999
250V
70.000
275V
70.000
300V
70.000
500V
40.000
Current transformation ratio: This is the device primary current value. Value may be
between 1 and 10,000 A. The secondary current is 5A in the CVM-96.
Period: This is the maximeter integration period and can vary between 1 and 60 minutes.
Window type: Type of window used to save the maximeter value, this can be fixed or sliding.
Unit: The maximum demand can be calculated with active power III, apparent power III,
current III or current by phase depending on the device.
Maximeter reset: When the button is pressed, the device maximeter resets to zero.
Selecting the type of voltage calculated.
Configuration of the "backlight" disconnection. The value should be between 0 and 99
seconds.
Use this selector to configure the type of distortion the device will calculate.
On clicking the button the energy counters on the device will reset to zero.