If you press the key after changing the last digit, it will jump back to the rst digit so you
can modify the previously programmed values again.
To validate the data, press for 3 seconds and the prog icon will disappear from the display.
Press key to access the next programming step.
Table 12: Parameter codes used to program the outputs�
Parameter Phase Code Phase Code Phase Code Phase Code
Phase-Neutral Voltage L1 01 L2 09 L3 17 - -
Current L1 02 L2 10 L3 18 - -
Active power L1 03 L2 11 L3 19 III 25
Inductive Reactive Power L1 04 L2 12 L3 20 III 26
Capacitive Reactive Power L1 05 L2 13 L3 21 III 27
Apparent power L1 06 L2 14 L3 22 III 28
Power factor L1 07 L2 15 L3 23 III 29
Cosine φ L1 08 L2 16 L3 24 III 30
% THD V L1 36 L2 37 L3 38 - -
% THD A L1 39 L2 40 L3 41 - -
Phase-Phase Voltage L1/2 32 L2/3 33 L3/1 34 - -
Frequency - 31 - - - - - -
Neutral current - 35 - - - - - -
Maximum current demand L1 45 L2 46 L3 47 III 44
Active Power Maximum
Demand
- - - - - - III 42
Apparent Power Maximum
Demand
- - - - - - III 43
In addition, there are some parameters (Table 13) that refer to the three phases at the same
time (OR function). If you have selected one of these variables, the alarm will be activated when
any of the three phases meets the programmed conditions.
Table 13:Multiple parameter codes for alarm programming�
Types of parameters Code
Phase-Neutral Voltage 200
Current 201
Active power 202
Inductive Reactive Power 203
Capacitive Reactive Power 204
Power factor 205
Phase-Phase Voltage 206
% THD V 207
% THD A 208
Apparent Power 209
49
Instruction Manual
CVM-C10