To enter or modify the kilowatts per pulse value, press the
key repeatedly, increasing the value of the ashing digit.
When the on-screen value is that desired, press the
key to
go to the next digit to modify the other values.
If you press the key after changing the last digit, it will jump back to the rst digit so you
can modify the previously programmed values again.
Example: To program 500 Wh per pulse: 000.500
To program 1.5 kWh per pulse: 001.500
Once the desired option has been programmed, press the key to validate the information
and thereby nish programming the unit.
Maximum programming value: 999999 KWh.
Minimum programming value: 000.001 KWh.
Programming by alarm condition
On this screen the parameter code for which you want an alarm
to be generated is selected, based on Table 12�
The key jumps between the different options.
Table 12: Parameter codes for alarm programming�
Parameter Code Parameter Code
Active power III 16 Line voltage III 45
III Inductive Power 17 Apparent power III 34
III Capacitive Power 18 Maximum Demand 35
Three-phase Cosine φ 19 Current III 36
Power factor III 20 Phase voltage III 44
Frequency 21
Once an alarm code has been selected and validated with the key you must enter the
maximum value of the alarm condition.