CONFIGURATION
4.4 TARIFFS
CVMk2 permits conguring up to 9 tariff. To access the tariff conguration screen, position the
cursor over Tariff and press SET.
Parameters that can be congured on this screen follow:
• No. of Tariff.: The number of tariff. Specify how many different tariff are going to be
congured.
• Synch.: Use the internal clock or calendar to manage tariff, select the CLOCK option. To
use an external signal to change tariff (activating static inputs for a CVMk2
expansion card), select the EXTERNAL option.
It is possible to load a yearly fee calendar to the memory. This calendar can only be saved from
the CIRCUTOR POWER STUDIO SCADA software. The calendar is stored in the memory and
is synchronised with the internal clock.
• No. In.: If EXTERNAL was selected in the previous option, Synch., specify the input for
the expansion card, which will receive the impulse for each one of the tariff
Since the CVMk2 expansion cards can be inserted in different positions, four digits have been
reserved to congure the inputs. The digits that occupy the most memory indicate the position
in which the inputs card is inserted in the CVMk2 measurement module.
The last digits correspond to the input number to be programmed for tariff 2.
WARNING: CVMk2 has an internal clock that you have to congure. The
device will work with this local hour but, if you communicate the device with
Power Studio the local time of the device will be changed to UTC hour.