Circutor computer SMART III-Fast Series Manual do Utilizador Página 20

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 108
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 19
3�5�7�- Leakage current connection, IΔ
Tomeasuretheleakagecurrent,anearthleakagetransformermustbeused,suchasWGS
Theleakagecurrenttransformermustbeconnectedsuchastomeasurethecurrentofthe
capacitorbank�Thiswilldetectanyleakageinthecapacitorsofthecapacitorbank�
~
TC
LOAD
CAPACITORS
S1
S2
P1
P2
I
S1
S1
S2
S2
IL1, IL2, IL3
Figure 9: Connection of the leakage current transformer (IΔ)�
NB: The earth leakage transformer must have a ratio of 500 turns. The maximum leakage cur-
rent that the unit can measure correctly is 1.5A AC, even though the maximum input is 5A AC
via the earth leakage transformer.
DonotoperatetheleakagecurrenttransformerwiththeComputer SMART III
FASTpoweredon�
20
Computer SMART III FAST
Instruction Manual
Vista de página 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 107 108

Comentários a estes Manuais

Sem comentários