Pressthe keytoaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,“5�27�-
SIMULATION SCREEN”�
5�12�-STATUSOFTHESTAGES
Thisparameterisrepeatedforeachofthe6or12
possiblestages,offeringtheopportunitytoforce
theirstatuswithoutpayingattentiontotheoperation
performedbytheactualunit�
Inordertoidentifywhichofthe12stagesisbeing
configured,thescreenshowsC1,C2,etc�
Theconfigurationoptionsforeachstageareasfollows:
AUTO:Thestatusofthestagedependsontheoperationperformedbytheunit�
On:StageforcedtoON,alwaysconnected�
OFF:StageforcedtoOFF,alwaysdisconnected�
On NC:StageforcedtoON,alwaysconnectedbutthesystemdoesnottakeinto
accountitsconnectedpower�
Bydefault,allthestagesareconfiguredasAUTO�
Onthemeasurementscreens,theforcedstatesofthestagesareshownbyactivatingthe
bottomlineofthecapacitorstatusbar�(“4�4�1� STATUS OF THE CAPACITORS”)
Pressthe keytoentereditingmode�Itisidentifiedbythe symbolandtheblinking
ofthedigitstobemodified�
The keyshowsthenextoption�
The keyshowsthepreviousoption�
The keyskipstothepreviousstage�
The keyskipstothenextstage�
Press tovalidatethedata;the symboldisappearsfromthedisplay�
Pressthe keytoaccessthenextprogrammingstep�
Ifnokeysarepressedfor5minutes,theunitswitchestothesimulationscreen,“5�27�-
SIMULATION SCREEN”�
86
Computer SMART III FAST
Instruction Manual