Connection type:
3U�3C: 3voltagesand3currents�
3U�1C: 3voltagesand1current�
2U�1U: 2voltagesand1current�
Phase
Cos φ III
L:Inductive/C:capacitive
+:consumed/-:generated
Pressthe keytoswitchtothenextscreenofresults�
Pressthe keytoexittheresultsscreen�
No� steps detected
Program
C/K factor
Cos φ III
L:Inductive/C:capacitive
+:consumed/-:generated
Pressthe keytoswitchtothepreviousscreenofresults�
Pressthe keytoexittheresultsscreen�
IfanyerrorsoccurduringtheexecutionofthePlug&Playfunction,theprocesswillbeaborted
andtheerrorswillbedisplayedonthescreen�Whenaparameterhasbeencalculatedcorrectly
beforetheerrorisdetected,itwillbedisplayedonthepreviouslyassignedline�Theerrorsthat
canoccurinthePlug&PlayfunctionareshowninTable 40�
Table 40: Code of Plug&Play errors�
Code Description
P00
TherearethreepossiblecausesthatcanpreventthePlug&Playprocess
fromstarting:
-Somestagesarecancelledbytheleakagecurrentalarm�
-Somestagesareforcedintheconguration "5�12�- STATUS OF THE
STAGES”�
P01
ErrorwhensearchingfortheConnectionType�Seeconnectiondiagrams�
P02
Phasenotfound�Cosineoutofrange(between0�62and0�99inductive)�
P03
Unstablemeasurement�Loadchangesduringtheprocess�